40002 - Cable tray SP 250x150 L=6 m incl. cover, clips and splice plate
Download datasheet – SP cable tray (PDF, English)
SP is a post-supported GRP cable troughing system for routing and protecting cables, including railway installations and locations with challenging terrain. The trough is supplied in 6 m lengths with a removable cover. Low weight, perforations and pre-assembled connectors facilitate installation.
SP250: 250 × 150 mm, L = 6 m. See the dimensioned cross-section and joint illustration in the image gallery.
The manufacturer’s installation text specifies a 6 mm gap between trough lengths and an 8 mm gap between covers. Support spacing and load must be checked for the specific installation.
Item no. 40002
Log in for prices and stock availabilityTechnical specifications
| System | EBO Systems SP |
| Dimensions (width × height) | 250 × 150 mm |
| Supplied length | 6 m |
| Trough and cover | Glass-reinforced plastic (GRP), material grade K23 |
| Joint | U-shaped connector in 316 stainless steel, pre-assembled on one side |
| Material properties | Corrosion-resistant, UV-resistant and halogen-free material |
| Fire behaviour | UL 94 V-0, stated for the K23 material in the manufacturer’s datasheet |
| Electrical property | The datasheet states a dielectric resistance of 30 kV for the material, with reference to IPH Berlin |
| Scope of supply | Cable trough with cover, clips and splice plate, as stated in the product name |
Installation and joints
The manufacturer’s installation text specifies a 6 mm gap between trough lengths and an 8 mm gap between covers. The joints use round-headed screws to reduce the risk of cable damage. The datasheet describes overlapping cover joints and Torx screws with cage nuts.
The system can be installed on hot-dip galvanised posts and adjustable post heads. These system components are not listed as included in this product’s scope of supply. Support spacing and permissible load must be checked for the specific project; the drawings with 3 m and 6 m support spacing are installation examples, not a general load approval.
Technical information is taken from the manufacturer’s SP datasheet, pages 114–119. Electrical material data does not specify an allowable operating voltage or provide a blanket exemption from earthing metallic system components. The product image shows a system example with cables and supports; dimensions and scope of supply are as specified above.